Generator Checklist

Generator test check list

 

 Created by Heriberto - Use this for reference in making Jotform. 

 

1- Test the generator with the PV and Grid off, and the battery SOC the same as (lower SOC limit).

          • Monitor voltage, frequency, and power.

  • System reading voltage ………………………. L1-L2 =        V t0    248.0   V
  • Multimeter reading voltage …………………. L1-L2 =    240.9   V to    241.4   V
  • System reading frequency ………………    60.8.3     Hz to     61.4    Hz
  • Multimeter reading frequency ………..     61.3      Hz to    61.4     Hz
  • Load Power …………………………………     0      Kw
  • Battery Power………………………………     1.8      Kw
  • Gen Power……...…………………………..     1.8      Kw

          • Verify wiring that is polarized …………………………      yes      .   

          • Check if the generator has a breaker correct ……      yes      .

          • Check drie contacts …………………………………….       working     .

          • Check Power Duty ……………………………………….       40%       .    

          •  Passed the test with the PV and Grid turned off?       No passed      .

2- Test the exercise function with different intervals and durations.

         • Reading with 5 min interval ................................     ok     .

         • Reading with 10 min interval …..………………………     ok      .

         • Reading with 15 min interval …..………………………    ok       .  

         • Monitoring voltage, frequency

  • System reading voltage …………………. L1-L2 =     248.4      V
  • Multimeter reading voltage ……………. L1-L2 =    240.7     V
  • System reading frequency………..    61.3      .Hz  to    61.7      .Hz
  • Multimeter reading frequency…..     61.4     .Hz  to     61.5      . Hz

       • Passed the exercise test?......................................       Passed      .